The IC693ALG222 is a 16-Channel Analog Voltage Input module for the GE Fanuc 90-30 Series. This PLC will give you 16 single-ended or 8 differential input channels. The Analog Input features easy-to-use configuration software for 2 input ranges: from -10 to +10 and 0 to 10 volt. This module converts the analog signals into digital signals. The IC693ALG222 receives two input signals which are unipolar and bipolar. The unipolar signal ranges from 0 to +10 V whereas bipolar signal ranges from -10V to +10V.This module can be set up in any of the I/O slots in a 90-30 Programmable control system. There will be connector block mounted on module for connecting to user devices.
The number of channels in the IC693ALG222 may be single ended (1 to 16 channel) or differential (1 to 8 channel). The power requirement for this module is 112mA from 5V bus, and also it requires 41V from 24V DC supply to power the converters. The two LED indicators indicate the status of user power supply the module's status. These two LEDs are MODULE OK, which gives the status regarding power-up, and POWER SUPPLY OK, which checks whether the supply is above the minimum required level. The IC693ALG222 module is configured either using logic master programming software or via Handheld programming. If the user chooses to program the module via Handheld programming, he can only edit active channels, not active scanned channels. This module uses the %AI data table to record analog signals for the use of the programmable logic controller.
No. of channels: | 1 to 16 single-ended or 1 to 8 differential |
Input Voltage Range: | 0 to +10V or -10 to +10V |
Calibration: | Factory calibrated to: 2.5mV per count or 5 mV per count |
Update Rate: | 6 msec (all 16) or 3 msec (all 8) |
Input Filter Response: | 41 hz or 82 Hz |
Power Consumption: | 112 mA from +5VDC bus or 41mA from +24 VDC bus |
Number of Channels | 1 to 16 selectable, single-ended 1 to 8 selectable, differential |
Input Voltage Ranges | 0 V to +10 V (unipolar) or -10 V to +10 V (bipolar); selectable each channel |
Calibration | Factory calibrated to: 2.5 mV per count on 0 V to +10 V (unipolar) range 5 mV per count on -10 to +10 V (bipolar) range |
Update Rate | Single Ended Input Update Rate: 5 ms Differential Input Update Rate: 2 ms |
Resolution at 0V to +10V | 2.5 mV (1 LSB = 2.5 mV) |
Resolution at -10V to +10V | 5 mV (1 LSB = 5 mV) |
Absolute Accuracy 1,2 | ±0.25% of full scale @ 25°C (77°F) ±0.5% of full scale over specified operating temperature range |
Linearity | < 1 LSB |
Isolation, Field to Backplane (optical) and to frame ground | 250 VAC continuous; 1500 VAC for 1 minute |
Common Mode Voltage (Differential)3 | ±11 V (bipolar range) |
Cross-Channel Rejection | > 70dB from DC to 1 kHz |
Input Impedance | >500K Ohms (single-ended mode) >1 Megohm (differential mode) |
Input Filter Response | 23 Hz (single-ended mode) 57 Hz (differential mode) |
Internal Power Consumption | 112 mA (maximum) from the backplane +5 VDC bus 110 mA (maximum) from the backplane isolated +24 VDC supply |