Specifications of Schneider Modicon Module BMXP341000


Main

range of product

Modicon M340 automation platform

product or component type

Processor module

number of racks

2

number of slots

11

discrete I/O processor capacity

512 I/O single-rack configuration

analogue I/O processor capacity

66 I/O single-rack configuration
128 I/O multi-rack configuration

number of application specific channel

20

monitoring

Diagnostic counters Modbus
Event counters Modbus


Complementary

control channels

Programmable loops

integrated connection type

Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS232C, transmission mode: 2 twisted shielded pairs at 0.3...19.2 kbit/s full duplex
Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3...19.2 kbit/s half duplex
Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS232C, transmission mode: 1 twisted shielded pair at 0.3...19.2 kbit/s half duplex
Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3...19.2 kbit/s half duplex
USB port at 12 Mbit/s

communication module processor capacity

2 Ethernet communication module
2 AS-Interface module

number of devices per segment

0…32 (character mode)
0…32 (Modbus)

number of devices

2 point-to-point character mode
2 point-to-point Modbus

bus length

0…10 m serial link non isolated character mode segment
0…10 m serial link non isolated Modbus segment
0…1000 m serial link isolated character mode segment
0…1000 m serial link isolated Modbus segment
0…15 m character mode point-to-point
0…15 m Modbus point-to-point

maximum tap links length

<15 m serial link non isolated character mode segment
<15 m serial link non isolated Modbus segment
<40 m serial link isolated character mode segment
<40 m serial link isolated Modbus segment

number of addresses

0…248 for character mode
0…248 for Modbus

requests

1 K data bytes per request character mode
252 data bytes per RTU request Modbus
504 data bytes per ASCII request Modbus

control parameter

One CRC on each frame (RTU) Modbus
One LRC on each frame (ASCII) character mode
One LRC on each frame (ASCII) Modbus

memory description

Internal RAM 2048 kB
Internal RAM 128 kB data
Internal RAM 1792 kB program constants and symbols
Supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data

maximum size of object areas

128 kB unlocated internal data
16250 %Mi located internal bits
32464 %MWi internal words located internal data
32760 %KWi constant words located internal data

default size of object areas

128 %KWi constant words located internal data
256 %Mi located internal bits
512 %MWi internal words located internal data

application structure

1 periodic fast task
32 event tasks
1 cyclic/periodic master task
No auxiliary task

execution time per instruction

0.18 µs Boolean
0.26 µs double-length words
0.38 µs single-length words
1.74 µs floating points

number of instructions per ms

4.2 Kinst/ms 65 % Boolean + 35 % fixed arithmetic
5.4 Kinst/ms 100 % Boolean

system overhead

0.2 ms for fast task
1.05 ms for master task

current consumption

72 mA at 24 V DC

supply

Internal power supply via rack

marking

CE

status LED

1 LED (green)processor running (RUN):
1 LED (red)I/O module fault (I/O):
1 LED (red)memory card fault (CARD ERR):
1 LED (red)processor or system fault (ERR):
1 LED (yellow)activity on Modbus (SER COM):

net weight

0.2 kg


Environment

ambient air temperature for operation

0…60 °C

relative humidity

10…95 % without condensation

IP degree of protection

IP20

protective treatment

TC

directives

2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
2012/19/EU - WEEE directive

standards

EN 61131-2
EN 61000-6-4
EN 61000-6-2
EN 61010-2-201


Offer Sustainability

Sustainable offer status

Green Premium product

REACh Regulation

REACh Declaration

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End of Life Information

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins



Related Viyork Industrial Automation Products

Start Now
Email us with any questions or inquiries or use our contact data. We would be happy to answer your questions.